Robot Alarm Codes 5334-5410 Repair

During the operation of the OTC DAIHEN Welding Robot, if the system experiences problems such as measurement point error, speed/current/voltage monitoring exception, adaptive weave amplitude, or ZF posture deviation, the teach pendant will usually display a hardware and control-level alarm in the 5334 to 5410 range. If these faults are not investigated promptly, they may cause serious operational safety hazards or damage to core components such as the reducer.

To help on-site engineers and mechanics quickly locate problems, we have organized the diagnostic terminology from the official maintenance manual to provide you with the following intuitive fault quick reference table. We recommend using the search function, entering the error code (e.g., 5334), to accurately obtain troubleshooting and processing suggestions.

I. OTC Robot Alarm Code Real-Time Quick Reference Table (5334-5410)

Alarm CodeFault PhenomenonFault Cause AnalysisCountermeasures & Solutions
5334Measurement Point ErrorThe measurement point was not acquired starting from point 1Q.Acquire the measurement point starting from point 1Q, and then perform an exception reset.
5335Measurement Point ErrorThe measurement point was not acquired starting from point 1A.Acquire the measurement point starting from point 1A, and then perform an exception reset.
5400Speed Monitoring Range Setting ExceptionAn exception occurs when the minimum value of speed monitoring exceeds the maximum value set in the adaptive control state.Check the minimum and maximum values of the speed monitoring value, and then reset the fault.
5401Current Monitoring Range Setting ExceptionAn exception occurs when the minimum value of current monitoring exceeds the maximum value set in the adaptive control state.Check the minimum and maximum values of the current monitoring value, and then reset the fault.
5402Voltage Monitoring Range Setting ExceptionAn exception occurs when the minimum value of voltage monitoring exceeds the maximum value set in the adaptive control state.Check the minimum and maximum values of the voltage monitoring value, and then reset the fault.
5403Adaptive State Setting ExceptionAn illegal setting of the adaptive state was changed in the tracking section, making it impossible to switch the validity and invalidity of the adaptive control in the tracking section.Determine the specified LSR file number and confirm the setting content, and then reset the fault.
5404Adaptive Weave Amplitude Too LargeThe weave amplitude specified by adaptive control exceeds the maximum weave amplitude display value of the adaptive control.Use WinUser to check the data table, increase the maximum weave amplitude display value for adaptive control, and then reset.
5406Exceeded ZF Posture Deviation RangeThe difference between the target posture calculated by the ZF command and the taught posture exceeds the posture deviation range.Check the target posture, modify (increase) the ZF parameter or change the program, and then reset the fault.
5408Maximum Distance in ZN Command Too LongThe target position calculated by the ZN command exceeds the movable area.Shorten the maximum distance in the ZN command, and then reset the fault.
5410Stability Waiting Time Too LongThe stability waiting time has been exceeded.Modify (increase) the Z.T stability waiting time to correct the error, and then reset the fault.

II. Get Professional Technical Support and Maintenance Services

When the robot frequently displays the above hardware-level alarms, and routine reset attempts are ineffective, do not forcefully pull the robot arm or repeatedly force restarts, so as not to cause secondary irreversible damage.

Contact Anhui Oujie for Technical Guidance

If you do not know how to handle such underlying alarms on-site, please take a picture of the error screen on the teach pendant and the on-site status, and send it to us via WhatsApp. As an OTC Designated Authorized Distributor, our professional maintenance engineers will provide you with a free technical assessment and troubleshooting solution!

Scroll to Top
Anhui Oujie Automation Technology Co., Ltd.
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.